Govi Parts
www.govi-units.com www.govi-units.nl
For products see links in navigation bar, this sheet is for information.
Govi trailer units, the right choice for you Trailer refrigeration.
Type GV-1600N
Arktik 1600N-2000N-2000P-2500N
Govi trailer unit set
Voltage
Type Temperature Volumen Capacity* Voltage
arktik 1600 N 0 ° C to + 10 ° C 12m³ 1600 Watt / 2 ° C 230V / 50Hz 0.855 kW
arktik 2000 N 0 ° C to + 10 ° C 19m³ 2050 Watt / 2 ° C 230V / 50Hz 1.07 kW
arktik 2500 N 0 ° C to + 10 ° C 27m³ 2500 Watt / 2 ° C 230V / 50Hz 1.2 kW
arktik 2000 P -20 ° C to + 10 ° C 11m³ 2050 Watt / -20 ° C 230V / 50Hz 1.2 kW
Arktik Trailer Unit
Cooling systems for stationary trailers (cooling trailer / refrigerated trailers)
Normal cooling (0 ° C to + 15 ° C)
Refrigerant R134a (1600N / 2000N) R404A (2500N / 2000P)
* The data is based on a set temperature of 2°C
The cooling is based on the following environmental variables: outside temperature 30°C, R.H. 50%
Insulation with a k-value of is recommended.
Serial in all trailer refrigerations
Automatic defrosting with electric tubular element.
Light switch for lamp in trailer.
Supplied with two keys for control panel.
Lamp armateur incl. 60 wat lamp.
Pre-wired cable for connecting door contact brackets.
Pre-wired cable for connecting a lamp.
Connection socket "with sealing cap.
Thermometer for reading the indoor temperature.
Lockable Control Panel.
Warranty Cooling unit Type GV-1600N 1 Year Manufacturer's warranty from Govi
Unit Connect /To turn on (2014 version)
Change setpoint (2014 version)
Manual defrost (2014 version)
www.govi-units.com www.govi-units.nl
Problems that you can check or solve yourself:
The fuse or circuit breaker trips. This depends on the voltage on the installation.
Normally there is 230V between the phase and neutral. P = U * I = 230 * 16 = 3680W
A B16 circuit breaker switches off immediately if a short-circuit current of 80A is measured (5*In).
A C16 switches off at 160A short-circuit current (10*In). A C16 is often used for machines with a high starting current.
It is also important that the temperature in your fuse box does not become too high. Above 25 degrees, the response value of the circuit breaker decreases.
A 16A circuit breaker can then switch off at a consumption of 13A.
Maintenance is important, and a refrigeration company is preferred.
for the sake of knowledge and safety, here are some tips:
Clean the condenser by carefully blowing through it with air and then with water.
Check the contacts and terminals annually and tighten them if necessary.
And check and clean the 220V plug and contra plug for good contact.
Replace them in case of heavy or damage or contamination.
Perform the cooling capacity test to check for possible gas shortage.
or poor operation.
For operational reliability, perform preventive maintenance as follows if necessary.
Replace the compressor starting capacitor after 3 years with intensive use.
Replace the condenser fan after 4 years and replace the evaporator motor after 5 years.
Replace the magnetic switch after 6 years.
Advice after 6 years in case of a refrigerant leak or refrigeration repair, replace the pressure sensor and dryer.